# Web UI – Channel Management

> Kanalsidan i Web UI — hitta, läs, sätt, konfigurera och charta varje kanal, med livevärden, statistik, filter och grupper.

_Källa: E-Sharp (esharp.se) · Accordion Web UI_


The **Channels** page lists every channel in the station, with live values. You use it to find a channel, read its value, set an output, see its statistics and trend, view its details, change its configuration and send it to the chart.

## Accessing

In the side menu click **Channels**, or click a module chip in the status bar to open the page filtered to that module's channels.

## The channel list

Each row is one channel (sorted by alias at first). Columns include **On** (enabled), **Group**, **Alias**, **Net name** (hidden by default), **Type**, **Dir** (IN/OUT/both), **Value**, **Unit**, **Min/Max/Mean** statistics, **Trend**, **Description** and **Device**, plus a **⋮** menu. Rows in *italics* are system channels — readable but not settable. On a narrow screen the less important columns drop out; on a phone each row becomes a card.

## Finding channels

- **Search all columns** matches any visible column (and the net name), in any case.
- **Column filters** under each title narrow by text or by picking values (Type, Dir, On). **Clear filters** removes them all.
- **Sort** by clicking a title (natural order, so `CH2` before `CH10`).
- **Group** by Group, Type, Dir or Device.
- **Columns** shows/hides columns; **Reset layout** returns to defaults.

## Live values

The list reads the on-screen channels repeatedly (off-screen channels are not read, keeping it fast). Controls: **Pause/Resume**, **Interval (ms)** (100–60000, default 1000; the chart uses the same interval), **Clear history** and **Reload**. A status shows what the list is doing (e.g. *24 live · 35 ms*, *pushed*, *Paused*, *Read failed*). The list updates by itself when channels are added, removed or reconfigured.

The **Value** column shows a number (with a light bar for volts on a 0–5 V scale and for percentages), a switch for digital channels (greyed when read-only), **N/A** for channels with no single value, and **…** while the first value arrives. Hover to see the exact reported value.

## Setting values

You can set a channel whose direction includes OUT and that is not a system channel:

- **Switches (digital)** — click the switch, press **Space**, or use **Toggle** in the menu.
- **Numbers** — click the value (or press **Enter**), type, press **Enter** to send (**Esc** cancels; comma or point both work).
- **Ratiometric** — typed in percent (`25` → 0.25 on the station).
- **Multiplexers** — pick a destination net from a drop-down.
- **Registers / text** — typed as text, sent exactly.
- **Several at once** — select rows (click, Ctrl/Cmd-click, Shift-click); setting a value applies it to every selected row that takes it. Only rows shown by the filters are changed.

## Keyboard

**Up/Down** move rows, **Space** toggles the focused switch, **Enter** opens the editor (and sends in the editor), **Esc** cancels or clears the selection.

## The row menu

Open with **⋮**, right-click, or press-and-hold. Items (only those that apply): **Read value**, **Toggle**, **Show in chart** / **Remove from chart**, **Acquire waveform…**, **Details**, **Configure…**, **Select/Deselect**, **Copy net name**, **Copy alias**.

**Details** lists everything the station reports about the channel. **Configure…** changes the channel's settings (only the fields you change are sent, and a confirmation lists each change). The configurable fields depend on the channel type — for example Analog (gain, offset, input config, default, resolution), Digital (push/pull type, default), UART (baud, bus type, termination byte), SPI (clock, mode, chip-enable high) and I²C (clock speed).

## Statistics, trend and memory

Min/Max/Mean are computed from the values read; a new min flashes red and a new max blue. **Trend** draws the last 50 values. Which columns are shown, the grouping, the sort and the interval are remembered in your browser; filters and the search are not, so a page you open later never hides rows without telling you why.

## See also

- [Web UI – översikt](/accordion/support/docs/webui-oversikt)
- [Web UI – Chart Viewer](/accordion/support/docs/webui-chart-viewer)
- [Web UI – Power & instrument](/accordion/support/docs/webui-power-instruments)
- [Web UI – Kalibrering](/accordion/support/docs/webui-kalibrering)